CORE PRODUCT CAPABILITIES
Core Structural Features of Fixed Panel-Type Radiators
The PG1200-27/520 is structurally configured for the fixed cooling requirements of oil-immersed transformers. Its value lies not only in increasing heat-dissipation surface area, but also in reducing sealing points, supporting fixed installation, and providing a foundation for outdoor coating protection.
Fully Welded Construction
The fully welded design reduces conventional sealing points and gasket use, helping lower the risk of oil leakage during long-term operation. Weld quality and sealing performance shall be verified according to product inspection requirements and project acceptance conditions.
Panel-Type Natural Cooling
Radiator panels form heat-transfer surfaces exposed to air, allowing heat from transformer oil to be released into the surrounding environment. The 17.61 m² natural cooling area is the baseline parameter for this model; actual cooling performance remains dependent on operating conditions.
Powder-Coated Corrosion Protection
The radiator is finished with RAL 7035 powder coating with a total film thickness of 180 μm, providing a basis for surface protection in outdoor environments. Available information indicates that this coating system can meet C4 corrosion-protection requirements; the applicable corrosion class shall be subject to order technical documents and test records.
Routine Maintenance Accessibility
The fixed structure reduces reliance on commonly consumed sealing materials and helps simplify routine maintenance considerations. During operation, the appearance, connections, coating condition, and oil circuit should still be inspected in accordance with transformer maintenance procedures.
APPLICATION CONDITIONS
Application Scenarios and Environmental Compatibility
This fixed transformer cooling component is suitable for oil-immersed transformer projects requiring permanent installation. For locations with high temperature and humidity, cold and damp conditions, dust, or certain corrosive factors, cooling area, coating system, installation layout, and site protection conditions should be evaluated together during product selection.
Urban and Rural Distribution Networks
Designed for 10 kV and 35 kV oil-immersed distribution transformers, providing fixed cooling support for conventional distribution equipment.
Pole-Mounted and Platform-Mounted Installations
Suitable for outdoor fixed installations. Equipment load capacity, interfaces, layout space, and site installation conditions should be checked before application.
Package Substations
Can be supplied as a cooling component for oil-immersed transformers in package substations, meeting fixed connection and outdoor protection requirements.
Industrial Specialty Transformers
May be used for rectifier transformers, traction transformers, and similar projects when technical conditions are compatible, subject to confirmation of thermal load and interface design.
Project Compatibility Note:
For hot and humid environments, project requirements may call for increased cooling area, an epoxy powder corrosion-protection system, optimized fin channels, and coordinated dustproof, waterproof, or anti-condensation design. These features shall be determined by project location, equipment structure, and technical agreement and are not standard for every order.